消防閥門發(fā)生內(nèi)漏怎么處理,?
來源:http://m.n3462.cn/ 日期:2022-04-20
消防閥是工業(yè)和建筑管道控制的重要配件,。主要產(chǎn)品控制精度高,特別是流量控制,。目前,,它廣泛應(yīng)用于工業(yè)控制系統(tǒng)中。在使用過程中,,經(jīng)常會(huì)有各種各樣的問題困擾著我們
Fire valve is an important accessory for industrial and building pipeline control. The main products have high control accuracy, especially flow control. At present, it is widely used in industrial control system. In the process of use, there are often various problems perplexing us
告訴我們消防閥內(nèi)部泄漏的原因和處理方法,。
Tell us the cause and treatment of internal leakage of fire valve.
從問題產(chǎn)生的原因及方案分析,
Analyze the causes and solutions of the problems,
消防器材公司的維修人員在加工或組裝過程中,,受工藝影響,,很可能造成電動(dòng)調(diào)節(jié)閥內(nèi)部泄漏。此時(shí),,主要是由于固定限位開關(guān)的動(dòng)作以及控制閥在運(yùn)行過程中控制介質(zhì)對(duì)控制閥的不斷沖刷和作用方式,,導(dǎo)致閥門無法關(guān)閉,,造成內(nèi)部泄漏。在這方面,,我們主要應(yīng)該調(diào)整限位開關(guān)的位置來這一現(xiàn)象,。
In the process of processing or assembly, the maintenance personnel of the fire equipment company are likely to cause internal leakage of the electric control valve due to the influence of the process. At this time, it is mainly due to the action of the fixed limit switch and the continuous scouring and action mode of the control medium on the control valve during the operation of the control valve, which makes the valve unable to close and causes internal leakage. In this regard, we should mainly adjust the position of the limit switch to solve this phenomenon.
的消防閥調(diào)試不當(dāng)導(dǎo)致內(nèi)部泄漏。由于電控閥的控制部分故障,,閥門的限位開關(guān)和過扭矩開關(guān)會(huì)導(dǎo)致密封面磨損或腐蝕,也會(huì)導(dǎo)致內(nèi)部泄漏,。在這方面,,我們?nèi)詰?yīng)努力調(diào)整限位開關(guān)。
Improper commissioning of the fire valve resulted in internal leakage. Due to the failure of the control part of the electric control valve, the limit switch and over torque switch of the valve will cause wear or corrosion of the sealing surface and internal leakage. In this regard, we should still strive to adjust the limit switch.
由于電動(dòng)執(zhí)行機(jī)構(gòu)調(diào)零不準(zhǔn)確,,閥門無法完全關(guān)閉,,出現(xiàn)內(nèi)部泄漏。主要調(diào)整方法是手動(dòng)關(guān)閉閥門,,或在無法擰緊后將閥門轉(zhuǎn)回半圈,,以調(diào)整調(diào)整極限。
Due to the inaccurate zeroing of the electric actuator, the valve cannot be completely closed and internal leakage occurs. The main adjustment method is to close the valve manually or turn the valve back half a turn after it cannot be tightened to adjust the adjustment limit.
通過向下推關(guān)閉閥門,。如果執(zhí)行機(jī)構(gòu)的推力不夠大,,閥門將無法完全關(guān)閉,并會(huì)發(fā)生內(nèi)部泄漏,。主要方案是更換高推力的執(zhí)行機(jī)構(gòu),。
Close the valve by pushing down. If the thrust of the actuator is not large enough, the valve will not be fully closed and internal leakage will occur. The main solution is to replace the actuator with high thrust.