干粉滅火系統(tǒng)組件設(shè)置以及要求
來(lái)源:http://m.n3462.cn/ 日期:2023-04-26
干粉滅火系統(tǒng),由干粉供應(yīng)源通過(guò)輸送管道連接到固定的噴嘴上,,通過(guò)噴嘴噴放干粉的滅火系統(tǒng),。下面
川消小編為您講解下干粉滅火系統(tǒng)組件設(shè)置以及要求事項(xiàng)吧。
The powder extinguishing system is a fire extinguishing system that connects a dry powder supply source to a fixed nozzle through a conveying pipeline, and sprays dry powder through the nozzle. Below, the editor of Chuanxiao will explain to you the component settings and safety requirements of the dry powder fire extinguishing system.
干粉滅火系統(tǒng)組件的設(shè)置要求
Requirements for setting up components of dry powder fire extinguishing systems
(一)儲(chǔ)存裝置
(1) Storage device
(1)干粉儲(chǔ)存容器應(yīng)符合現(xiàn)行標(biāo)準(zhǔn)《壓力容器技術(shù)監(jiān)察規(guī)程》的規(guī)定,;驅(qū)動(dòng)氣體儲(chǔ)瓶及其充裝系數(shù)應(yīng)符合現(xiàn)行標(biāo)準(zhǔn)《氣瓶監(jiān)察規(guī)程》的規(guī)定,。
(1) Dry powder storage containers should comply with the current national standard "Supervision Regulations on Safety Technology of Pressure Vessels"; The driving gas storage cylinder and its filling coefficient should comply with the current national standard "Gas Cylinder Safety Supervision Regulations".
(2)干粉儲(chǔ)存容器設(shè)計(jì)壓力可取1.6MPa或2.5MPa壓力級(jí);其干粉滅火劑的裝量系數(shù)不應(yīng)大于0.85,;其增壓時(shí)間不應(yīng)大于30s,。
(2) The design pressure of the dry powder storage container can be 1.6 MPa or 2.5 MPa pressure level; The loading coefficient of its dry powder extinguishing agent should not exceed 0.85; The pressurization time should not exceed 30 seconds.
(3)驅(qū)動(dòng)氣體應(yīng)選用惰性氣體,宜選用氮?dú)?;二氧化碳含水率不?yīng)大于0.015%(m/m),,其他氣體含水率不得大于0.006%(m/m);驅(qū)動(dòng)壓力不得大于干粉儲(chǔ)存容器的高工作壓力,。
(3) The driving gas should be inert gas, preferably nitrogen; The moisture content of carbon dioxide should not exceed 0.015% (m/m), and the moisture content of other gases should not exceed 0.006% (m/m); The driving pressure shall not exceed the high working pressure of the dry powder storage container.
(4)儲(chǔ)存裝置的環(huán)境溫度應(yīng)為-20~50℃,。
(4) The ambient temperature of the storage device should be -20~50 ℃.
(二)選擇閥和噴頭
(2) Selection valve and nozzle
(1)系統(tǒng)啟動(dòng)時(shí),選擇閥應(yīng)在輸出容器閥動(dòng)作之前打開(kāi),。
(1) When the system starts, the selector valve should be opened before the output container valve acts.
(2)噴頭的單孔直徑應(yīng)大于或等于6mm,。
(2) The single hole diameter of the nozzle should be greater than or equal to 6mm.

干粉滅火系統(tǒng)使用要求
Safety requirements for the use of dry powder fire extinguishing systems
1.防護(hù)區(qū)內(nèi)及入口處應(yīng)設(shè)火災(zāi)聲光警報(bào)器,防護(hù)區(qū)入口處應(yīng)設(shè)置干粉滅火劑噴放指示門(mén)燈及干粉滅火系統(tǒng)性標(biāo)志牌,。
1. Fire sound and light alarms should be installed inside and at the entrance of the protection zone, and dry powder fire extinguishing agent spraying indicator door lights and permanent signs of the dry powder fire extinguishing system should be installed at the entrance of the protection zone.
2.防護(hù)區(qū)的走道和出口,,必須保證人員能在30s內(nèi)疏散。
2. The walkways and exits of the protective zone must ensure that personnel can safely evacuate within 30 seconds.
3.防護(hù)區(qū)的門(mén)應(yīng)向疏散方向開(kāi)啟,,并應(yīng)自行關(guān)閉的功能,。
3. The door of the protective zone should open in the direction of evacuation and have the function of self closing.
4.防護(hù)區(qū)入口處應(yīng)裝設(shè)自動(dòng)、手動(dòng)轉(zhuǎn)換開(kāi)關(guān),。轉(zhuǎn)換開(kāi)關(guān)安裝高度宜使中心位置距地面1.5m,。
4. Automatic and manual transfer switches should be installed at the entrance of the protection zone. The installation height of the transfer switch should be such that the center position is 1.5m above the ground.
5.地下防護(hù)區(qū)和無(wú)窗或設(shè)固定窗扇的地上防護(hù)區(qū),,應(yīng)設(shè)置獨(dú)立的機(jī)械排風(fēng)裝置,排風(fēng)口應(yīng)通向室外,。
5. Underground protection areas and above ground protection areas without windows or with fixed window sashes should be equipped with independent mechanical exhaust devices, and the exhaust outlets should lead to the outdoors.
6.局部應(yīng)用滅火系統(tǒng),,應(yīng)設(shè)置火災(zāi)聲光警報(bào)器。
6. Local fire extinguishing systems should be equipped with sound and light fire alarms.
7.當(dāng)系統(tǒng)管道設(shè)置在有炸危險(xiǎn)的場(chǎng)所時(shí),,管網(wǎng)等金屬件應(yīng)設(shè)防靜電接地,,防靜電接地設(shè)計(jì)應(yīng)符合現(xiàn)行有關(guān)標(biāo)準(zhǔn)規(guī)定。
When the system pipeline is installed in a place with explosion risk, metal parts such as the pipeline network should be equipped with anti-static grounding, and the anti-static grounding design should comply with the current national standards and regulations.
干粉滅火系統(tǒng)組件設(shè)置以及要求就講解到這里了,,您對(duì)此有怎樣的疑惑或者需求,,就來(lái)我們網(wǎng)站
http://m.n3462.cn了解吧!
That's all for the component settings and safety requirements of the dry powder fire extinguishing system. If you have any doubts or needs about this, please come to our website http://m.n3462.cn Understand!