檢查消防器材設備系統(tǒng)我們需要注意什么,?
來源:http://m.n3462.cn/ 日期:2022-03-15
在流行期間,,公司大多處于恢復工作的初期,這是對自動火災報警和火災聯(lián)動控制系統(tǒng)進行測試和調(diào)試的有利時機,。公司應檢查火災報警控制器的主菜單,,以檢查自動火災報警系統(tǒng)
During the popular period, most companies are in the early stage of resuming work, which is a favorable opportunity to comprehensively test and debug the automatic fire alarm and fire linkage control system. The company shall check the main menu of the fire alarm controller to check the automatic fire alarm system
是否有故障,火災報警,,動作和防護罩,。等信息。檢查火災探測與報警系統(tǒng),,火災聯(lián)動控制系統(tǒng),,可燃氣體探測與報警系統(tǒng)以及電氣火災監(jiān)控系統(tǒng)的工作狀態(tài)。
Whether there is fault, fire alarm, action and protective cover. And other information. Check the working status of fire detection and alarm system, fire linkage control system, combustible gas detection and alarm system and electrical fire monitoring system.
消防器材廠家
Fire fighting equipment manufacturer
檢查雙電源的開關狀態(tài),,并檢查火災報警控制器主備電源的工作狀態(tài),。并切斷主電源,,測試備用電源是否可以正常供電。
Check the switching state of dual power supply and the working state of main and standby power supply of fire alarm controller. Cut off the main power supply and test whether the standby power supply can supply power normally.
還應測試火災探測器的火災報警和故障報警功能,。手動觸發(fā)手動報警按鈕,,檢查火災報警控制器輸出的火災報警信號和手動報警按鈕報警確認燈的顯示
The fire alarm and fault alarm functions of the fire detector shall also be tested. Manually trigger the manual alarm button and check the fire alarm signal output by the fire alarm controller and the display of the alarm confirmation light of the manual alarm button
滅火系統(tǒng)消防器材公司應檢查消防水池,消防水箱和補充水的消防設備的水位是否正常,,閥門是否打開,,管道是否生銹以及是否存在結露。是接口泄漏,。在寒冷地區(qū),,檢查滅火水是否凍結,防凍措施是否完好有效,。
The fire fighting equipment company of the fire extinguishing system shall check whether the water level of the fire pool, fire water tank and fire fighting equipment of make-up water is normal, whether the valve is opened, whether the pipeline is rusted and whether there is condensation. It's an interface leak. In cold areas, check whether the fire extinguishing water is frozen and whether the anti freezing measures are intact and effective.
手動啟動穩(wěn)定泵和消防水泵的主泵和備用泵,,以檢查泵組是否運行平穩(wěn),并手動停止,。模擬主泵故障,,檢查備用泵的自動切換啟動,并檢查儀器的顯示和指示燈,。還需要遠程自動和手動啟動和停止消防控制室中的每個消防水泵,以檢查水泵的動作和反饋信號,。
Manually start the main pump and standby pump of stabilization pump and fire pump to check whether the pump set operates stably and stop manually. Simulate the failure of the main pump, check the automatic switching start of the standby pump, and check the display and indicator light of the instrument. It is also necessary to remotely start and stop each fire pump in the fire control room automatically and manually to check the action and feedback signal of the water pump.